The 3-Dimensional Mapping of the Magnetic Field |
|
Theoretical Modeling Results
The first step in
producing the theoretical distributions required the derivation of a generalized
equation describing the magnetic field at some arbitrary point above the
TMS coil. To simplify the problem, the TMS coil was cut into finite
line segments and the equation to calculate the magnetic field due to such
a segment was determined. The complete derivation of the magnetic
field for a finite line segment is shown in Appendix
I. Once this equation was determined, the magnetic field at that point
in space due to the TMS coil is simply the integral of the magnetic field
due to each of the line segments. A C program was written to do the
calculations. Once the program was written and tested, a theoretical
investigation into the magnetic field distribution for the TMS coil was
done. Initially, only one lobe was tested.
This allowed us to investigate what the pointed region of the coil would do to the magnetic field. Figures 15, 16 and 17 illustrate the theoretical distribution for one lobe. The results indicate that the distribution is very similar to a simple circular coil except that for close distances from the coil there is a prominent peak at the points where there is a bend in the coil. The peak seems to diminish as the distance above the point becomes greater. |
(Click image to view enlarged version)
The programs were then used to investigate the complete TMS coil configuration. Figures 18, 19 and 20 illustrates the results obtained for the complete TMS coil. The theoretical distributions were completed with the Cadwell Current Supply set at 100% power output. |
Experimental Results
An image of the output
voltage carrying with time was seen on an oscilloscope (detected with a
single loop pick up coil). The signal was a cosine with a peak to
peak voltage of 50 +/- 1mV and a period of 200+/- 2![]() The SMP was used to collect the data for all three components of the magnetic field simultaneously. The data for the three components were saved in independent files and the proper conversion into voltage was done by converting the DAC output into voltages according to the calibration curve for the DAC. Once the voltage is known, the magnitude of the magnetic field was calculated for each data point by noting that the voltage measured is the integrated voltage over the effective surface area. The conversion factor in terms of the integrating circuit ws determined to be 6 X 10-3+/- 2 X 10-3 . This factor comes from the analysis of the integrator as shown in the Set Up section. We know that ![]() and ![]() where R is the resistor in the integrator, C is the capacitor and i is the current. Vin is the input voltage and Vo is the output voltage. Therefore, Combining all of these together we get a conversion factor in the form ![]() where B is the magnetic field. The voltage reading from the DAC was converted to voltage with the conversion factor of 1/204.8. The error on the magnetic field reading was determined by the conventional error analysis techniques. That is, the resistor was assumed to have an error of 10% and the capacitor to have an error of 50% which is often the case. Therefore, the equation for the error was determined to be: ![]() where r is the radius of the effective area, V is the voltage reading from the DAC, C is the capacitor and R is the resistance. Figure 21 depicts the x components of the magnetic field at a distance of 1.1 +/- 0.5cm as determined experimentally from the SMP. |
(Click image to view enlarged version)
The distance is defined with respect
to the coil center, - i.e. center of the junction of the two tear shaped
elements of the figure-eight coil. The power on the Cadwell Stimulator
was set at 50% of the maximal power output because the coil had overheating
problems. The current in the theoretical calculations for the program
was determined by taking the total current at maximal power output and
multiplying by ![]() The x component of the field was determined by orientation A of the SMP and the y component by orientation B of the SMP. Finally, the z component of the magnetic field was determined by orientation C of the SMP. Figures 21, 22, and 23 illustrates the results of each of the components of the magnetic field measured. The square root of the squared sums of the three components would give us the 3-dimensional magnitudes of the magnetic field for some distance above the coil. Figure 24 gives the experimental magnetic field distribution for a distance of 1.1 +/- 0.5cm above the TMS coil. Figure 25 illustrates the theoretical distribution expected. |
(Click image to view enlarged version)
The z component required an overall multiplication
factor of 0.8 since the amplifier in the circuit that was used for this
collection was slightly higher than the other two circuits. This
was determined by taking measurements at a specific point for the three
components through each of the circuits. If all of the circuits functioned
equally, then the readings should have been the same regardless of the
circuits. It was found that this was not the case for the circuit
connected to the z component SMP. Upon proper scaling, the total
distribution of the magnetic field produced by the TMS at a distance of
1.1 +/- 0.5cm was determined to be as shown in Figures 24.
The distribution was determined to have the shape that was expected from the theoretical calculations. The prominent peak was found to have a magnitude of 0.4 +/- 0.24 Tesla at this distance experimentally. There seems to be a discrepancy between the theoretical and the experimental results in terms of the magnitude. At a distance of 1.6 +/- 0.5cm, the distribution became more rounded in nature and the peak field diminished to 0.3 +/- 0.18T. The theoretical peak intensity was found to be 0.45 T for this distance. Figure 26 illustrates the resulting magnetic field distribution for 1.6 +/- 0.5cm above the coil and the corresponding theoretical distribution is shown in Figure 27. |
(Click image to view enlarged version)
At a distance of 2.1 +/- 0.5cm, the prominent focusing peak had a peak intensity of 0.30 +/- 0.20T and the theoretical peak intensity was determined to be 0.30T. Figure 28 illustrates the experimental results and Figure 29 illustrates the theoretical predictions of the 3-dimensional magnetic field distributions for the TMS coil. Once again, the power from the Cadwell was set at 50% of the maximal power output due to the TMS coil's persistent overheating. |
(Click image to view enlarged version)